KE300A Inverter Parameter Description
126
Time (t)
Any arrival current
Any arrival current amplitude
OFF
OFF
ON
ON
ON
OFF
Any arrival current detection
signal DO or Relay
Any arrival current amplitude
Output current
Figure 6-22 Any arrival current detection diagram
P8-42
Timing function selection
Factory default
0
Setting range
0
Invalid
1
Valid
P8-43
Timing running time selection
Factory default
0
Setting range
0
P8-44
1
AI1
2
AI2
3
Keypad potentiometer
P8-44 Analog input scale 100% corresponds to P8-44
P8-44
Timing running time
Factory default
0.0Min
Setting range
0.0Min ~ 3600.0Min
The parameters are used to set the inverter timing running function.
When P8-42 timing function selection is valid, timing starts after the inverter starts, reaches the setting
timing running time, the inverter stops automatically, meantime, DO terminal outputs ON signal.
Timing starts from 0 when the inverter starts, timing remain running time can be viewed via U0-20.
The timing running time is set by P8-43, P8-44, time unit is minute.
P8-45
AI1 input voltage protection lower limit
Factory default
3.10V
Setting range
0.00V ~ P8-46
P8-46
AI1 input voltage protection upper limit
Factory default
6.80V
Setting range
P8-45 ~ 10.00V
When the analog input AI1 value is bigger than P8-46, or smaller than P8-45, DO terminal outputs “AI1
input over limit” ON signal, used to indicate whether AI1 input voltage is in the setting range.
P8-47
Module temperature arrival
Factory default
75
℃
Setting range
0
℃
~ 100
℃