KE300A Inverter Parameter Description
104
Group P5 Output Terminal
The standard inverter has 2 multifunctional analog output terminals, 2 multifunctional relay output terminals,
1 HDO terminal (can be used as either high-speed pulse output terminal or collector open output).
P5-00
HDO terminal output selection
Factory default
0
Setting range
0
High speed pulse output
1
Open collector output
HDO terminal is programmable multiplexing terminal, can be used as high-speed pulse output, with
maximum frequency 100.00 kHz. Refer to P5-06 for details.
P5-01
HDO open collector output selection
Factory default
0
P5-02
Relay 1 output function selection
Factory default
2
P5-03
Relay 2 output function selection
Factory default
0
The parameters are used to select the functions of 3 digital outputs.
Multifunctional output terminal function selection is as follows:
Setting
value
Function
Description
0
No output
The output terminals do not have any functions.
1
Inverter is running
It indicates the inverter is running, and there is output frequency
(can be zero), and the inverter outputs ON signal at this time.
2
Fault output (fault stop)
When the inverter is faulty & it stops, it outputs ON signal.
3
FDT1 output
Please refer to P8-19 and P8-20 for details.
4
Frequency arrival
Please refer to P8-21 for details.
5
Zero speed running (no
output when stop)
When the inverter is running & the output frequency is 0, it
outputs ON signal. When the inverter stopped, the signal is
OFF.
6
Motor overload
pre-alarm
Judgment will be made according to the pre-warning threshold
value before the motor overload protection action. If it exceeds
the pre-warning threshold, it will output ON signal. Motor
overload parameters are set in P9-00 to P9-02.
7
Inverter overload pre-
alarm
The inverter outputs ON signal 10s before overload protection
action
8
Setting count value
arrival
When the counting value reaches the setting value of PB-08, it
outputs ON signal.
9
Designated count value
arrival
When the counting value reaches the setting value of PB-09, it
outputs ON signal. Refer to Group B function description for the
counting function.
10
Length arrival
When the measured actual length exceeds the setting value of
PB-05, it outputs ON signal.
11
PLC circulation
completion
When the simple PLC has been running for one cycle, it outputs
a pulse signal with width of 250ms.
12
Accumulated running
time arrival
When the accumulated running time of the inverter exceeds the
setting time P8-17, it outputs ON signal.
13
Frequency limiting
When the setting frequency exceeds the frequency upper limit
or frequency lower limit, and the output frequency of the
inverter reaches the frequency upper limit or frequency lower