KE300A Inverter Parameter Description
156
Figure 6-33 Double-speed over-current stall action diagram
Note:
1. Over-current stall action current 180% means 1.8 times of the rated current of inverter;
2. For high-power motors with carrier frequency below 2 kHz, due to the increasing of the pulse current, the
wave-by-wave current-limit response starts before the over-current stall action, and the torque is
insufficient. In this case, reduce the over-current stall action current.
A9-08
PID double-speed coefficient
Factory default
1
Setting range
1
~
200
PID adjustment is too slow in some applications, adjust this parameter, PID output value = the original PID
output value * this parameter.
A9-09
AO1 output analog signal selection
Factory default
0
Setting range
0
0-10V
1
4-20mA
A9-10
AO2 output analog signal selection
Factory default
0
Setting range
0
0-10V
1
4-20mA
If the field needs 4mA ~ 20mA analog output, the corresponding signal source for AO1, AO2 output analog
signal (A9-09, A9-10) need to be selected, no need to set the zero-offset coefficient (P5-10
、
P5-12). The
analog output deviation is corrected by the corresponding P5-11 and P5-13 gains.
Over-surrent stall
action current
Rated
frequency
Double rated
frequency
Over-surrent stall action current
=(fn/fs) k limitCur
*
*