KE300A Inverter Parameter Description
160
P8-43 and P8-44).
Code
Name
Range
U0-21
AI1 voltage before calibration
0.00
~
10.57V
U0-22
AI2 voltage before calibration
0.00
~
10.57V
U0-23
Keypad potentiometer voltage
before calibration
0.00
~
10.57V
U0-21 displays the sampling voltage of analog input 1(AI1).
U0-22 displays the sampling voltage of analog input 2(AI2).
The actual input voltage is corrected value after linear calibration, so as to reduce the deviation between
sampling voltage and the actual input voltage.
U0-09 and U0-10 display the actual voltages.
Code
Name
Range
U0-24
linear velocity
0
~
65535 m/min
U0-24 displays the sampling linear velocity of High-speed-pulse input (HDI). The unit is meter per minute
(m/min).
It can be calculated according to number of the actual sampling pulse and PB-07(number of pulse per
meter).
Code
Name
Range
U0-27
HDI input pulse fre.
0
~
65535Hz
U0-27 displays the sampling frequency of High-speed-pulse input (HDI). The unit is 1 Hz. Actually, U0-27
displays the same data with U0-18. The only difference is the unit.
Code
Name
Range
U0-28
Communication setting value
-100
~
100%
U0-28 displays the data written to address 0X1000.
Code
Name
Range
U0-29
Reserved
-
Code
Name
Range
U0-30
Main fre. A display
0.00
~
320.00Hz
U0-30 displays the frequency of main reference-input-channel (Refer to P0-03).
When P0-22 is set to 1, the range is -3200.0 to 3200.0 (Unit: Hz).
When P0-22 is set to 2, the range is -320.00 to 320.00 (Unit: Hz).