KE300A Inverter Parameter Description
146
PC-17
Simple PLC storage selection when
power-down
Factory default
00
Setting
range
Units place When power-off
0
Not store
1
Store
Tens place When stop
0
No store
1
Store
PLC storage when power-off means the last PLC running phase and running frequency are memorized
before power-off, keep running from the memory status after power-on next time.
When selection is “not store”, restart PLC process after power-on each time.
“PLC storage when stop” means the last PLC running phase and running frequency are memorized when
stopping, keep running with the memory status after power-on next time. When selection is “not store”,
restart PLC process after power-on each time.
PC-18
0th phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)
PC-19
0th Phase ACC/DEC time selection
Factory default
0
Setting range
0 ~ 3
PC-20
1st Phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)
PC-21
1st Phase ACC/DEC time selection
Factory default
0
Setting range
0 ~ 3
PC-22
2nd Phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)
PC-23
2nd Phase ACC/DEC time selection
Factory default
0
Setting range
0 ~ 3
PC-24
3rd Phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)
PC-25
3rd Phase ACC/DEC time selection
Factory default
0
Setting range
0 ~ 3
PC-26
4th Phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)
PC-27
4th Phase ACC/DEC time selection
Factory default
0
Setting range
0 ~ 3
PC-28
5th Phase running time
Factory default
0.0s (m)
Setting range
0.0s (m) ~ 6500.0s (m)