KE300A Inverter Function Parameter List
53
Function
code
Name
Detailed instruction
Factory
default
Modify
6: Min (AI1, AI2)
7: Max (AI1, AI2)
Full scale of 1-7 selection corresponds
to P2-10
P2-10
Torque upper limit
digital setting
0.0% ~ 200.0%
150.0%
○
P3 Group: V/F Control Parameters
P3-00
V/F curve setting
0: Linear
1: Multiple-point
2: Square
3: 1.2 power
4: 1.4 power
6: 1.6 power
8: 1.8 power
0
◎
P3-01
Torque boost
0.0: auto
0.1% ~ 30.0%
Model
depend
○
P3-02
Torque boost
cutoff frequency
0.00Hz ~ P0-10 (max. frequency)
50.00Hz
◎
P3-03
V/F frequency point 1
0.00Hz ~ P3-05
0.00Hz
◎
P3-04
V/F voltage point 1
0.0% ~ 100.0%
0.0%
◎
P3-05
V/F frequency point 2
P3-03 ~ P3-07
0.00Hz
◎
P3-06
V/F voltage point 2
0.0% ~ 100.0%
0.0%
◎
P3-07
V/F frequency point 3
P3-05 ~ P1-04 (motor rated power)
0.00Hz
◎
P3-08
V/F voltage point 3
0.0% ~ 100.0%
0.0%
◎
P3-09
V/F slip compensation
gain
0.0% ~ 200.0%
0.0%
○
P3-10
V/F over excitation gain
0 ~ 200
64
○
P3-11
V/F oscillation
suppression gain
0 ~ 100
Model
depend
○
P3-12
V/F oscillation
suppression mode
0~1
0
◎
P4 Group: Input Terminal
P4-00
D1 terminal function
0: No function
1: Forward (FWD)
2: Reverse (REV)
3: Three-line running control
4: Forward Jog (FJOG)
5: Reverse Jog (RJOG)
6: Terminal UP
7: Terminal DOWN
1
◎
P4-01
D2 terminal function
2
◎
P4-02
D3 terminal function
0
◎
P4-03
D4 terminal function
0
◎
P4-04
D5 terminal function
0
◎
P4-05
D6 terminal function
0
◎