KE300A Inverter Parameter Description
140
PA-26
PID feedback lost detection value
Factory default
0.0%
Setting range
0.0%: No judgment for feedback lost
0.1% ~ 100.0%
PA-27
PID feedback lost detection time
Factory default
1.0s
Setting range
0.0s ~ 20.0s
The parameters are used to judge whether PID feedback lost or not.
When PID feedback is smaller than feedback lost detection value (PA-26), lasts for longer than PID
feedback lost detection time (PA-27), the inverter alarms fault E-31, and handles according to the chose
fault process mode.
PA-28
PID stop calculation
Factory default
1
Setting range
0
No calculation when stop
1
Calculation when stop
This parameter is used to select PID stop status & whether PID continues calculating or not. For normal
applications, PID should stop calculating when stop.