46 – Control CS 320 FU / Rev.A 1.01
Function
Description
Adjustment
options
Factory setting
INPUT 3
Selection of a function that should be assigned to input 3 (X10/1-3).
OFF:
Not active
MOD4:
Week timer
MOD21: Brake actuation monitoring
MOD22: (analogous to input 1/MOD22)
NOTE:
If MOD14 - 16 is set at relay 4, MOD 21 (brake monitoring) is automatically set at
input 3. This setting cannot be changed if the brake mode is active.
OFF
MOD4 / MOD21/
MOD22
MOD4
SKS3
Setting for channel 1 of the pluggable signal transmission system (X20).
OFF:
Not active
MOD2:
Activates as closing edge protection in DOWN direction.
MOD3:
Activates as closing edge protection in UP direction.
MOD4:
Activates as safety device (internal safety circuit)
If the pluggable component of the signal transmission system is plugged into X20, the
controller recognises this (only during initial commissioning or after a reset) and the
parameter is automatically set to MOD4.
A - (teaching)
OFF
MOD2 – MOD4
A
SKS4
Setting for channel 2 of the pluggable signal transmission system (X20).
Selection mode analogous to the settings under SKS 3.
A - (teaching)
OFF
MOD2 – MOD4
A
RUNNING-
TIME
Monitoring the maximum running time of an UP or DOWN movement.
During the teach-in run, the runtime of the door is learned automatically.
If the deviation is 20% (in both directions), a runtime error appears.
After automatic teach-in, the runtime can be changed manually.
A (teaching)
OFF
1 – 300 seconds
A
REVERS.TIME
Motor standstill time with each direct change of direction.
The reversal time when the safety edge is activated during the closing movement is
one quarter of the set time.
100 –
5000 milliseconds
300
LIMIT SW.
Selection of the limit position system to be evaluated.
MOD1:
Absolute value encoder (AWG)
MOD2:
Mechanical limit switches (MEC)
MOD4:
only for frequency converter operation
MOD5:
Absolute value encoder (AWG) + mechanical limit switch DOWN (NC)
with standard installation
MOD6:
Absolute value encoder (AWG) + mechanical limit switch DOWN (NC)
with special installation with left rotating field
MOD 5+6 (optional):
Here an additional external mechanical limit switch is set to query the lower end point
in order to compensate for tolerances caused by the door mechanism and/or the door
curtain. As soon as the mechanical limit switch is actuated, the lower end position is
considered reached, regardless of the information from the absolute encoder.
A (teaching)
MOD1 – MOD2
MOD4 – MOD6
A
Functional overviews