44 – Control CS 320 FU / Rev.A 1.01
Function
Description
Adjustment
options
Factory setting
REVERSE OFF
Reversing point. Point at which the reversing of the door is switched off.
Only appears with systems with an electronic limit position system (AWG). Setting in
increments, starting from bottom limit switch-off point. In the case of systems with
mechanical limit switches, the supplementary limit switch DOWN serves as reversing
point.
A (teaching)
1 – 1000
50
LIGHT BARR. 1
Light barrier 1, with or without testing, mounted in passage area of the door.
Connection to X4 / 1-4. The respective system connected is automatically detected and
taught.
➔
Wiring diagrams „5.10 Connection of closing edge protective device 1“ on page
15
MOD1:
2-wire-system (MFZ)
with testing
MOD2:
3-wire-system NPN without testing
MOD3:
3-wire-system PNP without testing
4-wire-system NC contact
without testing
MOD4:
3-wire-system NPN with testing
MOD5:
3-wire-system PNP with testing
4-wire-system NC contact
with testing
NOTE:
If a 3- or 4-wire-system is operated with testing, the respective MOD (4 or 5) must be
set manually.
A (teaching)
MOD1 – MOD5
A
LB FUNC. 1
Function of the light barrier 1 in passage area of the door.
DOWN door movement
UP door movement
MOD1:
Stop + reversing
No action
MOD2:
Stop + rev
No action
MOD3:
STOP
No action
MOD4: STOP
STOP
MOD5:
Stop + reversing
Ride-along suppression
(UP door movement only possible if
the light barrier is clear).
MOD6:
No action
Stop + reversing
MOD7:
No action
Stop + rev
MOD8:
No action
Stop
MOD9:
Ride-along suppression
Stop + reversing
(DOWN door movement only possible,
if the light barrier is clear).
MOD1 – MOD9
MOD1
LB FUNC. 2
Function of the light barrier 2 in passage area of the door.
Only appears when setting parameter INPUT 1 = MOD15.
Connection only as NC contact via programmable input 1 (X4 / 9+10).
Selection mode analogous to the settings under LB FUNC. 1
MOD1 – MOD9
MOD1
LB POINT
Between limit position DOWN and LB POINT, the light barrier 1 (X4 / 1-4) is not
evaluated. Setting in increments, starting from bottom limit switch-off point.
Only appears with systems with an electronic limit switch.
Note:
At the first approach during adjustment, this point is automatically detected,
provided that light barrier 1 is mounted in the door frame and remains interrupted
during the downward travel from this point to the limit position DOWN.
A (teaching)
1 – UP SWITCH
A
IMPULS
Selection of a function that should be assigned to the impuls button (X3 / 7+8).
MOD1:
UP - STOP - DOWN - STOP - UP … (sequential control)
MOD2:
UP when door is stationary / no action during UP movement
Stop and run open with DOWN movement
MOD3:
UP when door is stationary / STOP with door movement
MOD4:
UP when door is stationary / no action with door movement
MOD5:
UP when door is stationary / DOWN from UP limit position
MOD1 – MOD5
MOD1
Functional overviews