22 – Control CS 320 FU / Rev.A 1.01
Control CS 320 FU / Rev.A 1.01 – 23
Connection of the brake monitoring module
A
C
B
D
1
2
4
3
1
2
3
4
5
6
7
8
X5
M
X10
XB1
5.13 / 4
Legend:
A
Brake monitoring module BWM 1
B
Brake rectifier
C
Drive brake
D
Brake power supply (AC)
NOTE:
If MOD14-16 (brake actuation) is set on relay 4, the mode for
the brake monitoring module is automatically set at input 3. If
a timer is used, this setting must be adapted to set the MOD
for the timer at input 3.
Optionally, input 3 can also be used for monitoring an
external load contactor and the drive brake.
The parameter INPUT 3 must then be set to MOD22.
Connection for monitoring an external load contactor
and drive brake (optional)
If the power of the door drive/frequency inverter used exceeds
the maximum load capacity of the internal contactor, an
external load contactor must be used.
In this case, it is possible to monitor the external load
contactor and drive brake with input 3 and therefore
guarantee safe operation.
1
L1
3
L2
5
L3
13
NO
A1
2
T1
4
T2
6
T3
14
NO
A2
+ 5V
GND
IN
X10
61
NO
62
NC
53
NO
54
NC
➞
5.13 / 5
The wiring preparation is carried out in the factory.
Installation