Control CS 320 FU / Rev.A 1.01 – 53
F.
Movement signal
MOD
Description
Remarks
MOD29
Door drives open.
Active with movement in the OPEN direction.
MOD30
Door drives closed.
Active with movement in the CLOSE direction.
MOD43
Door drives open or closed.
Active with all movement.
The brake monitoring module BWM 1 is not active with this setting!
G.
Functions for external accessories
MOD
Description
Remarks
MOD13
Magnetic lock function
The relay closes before every door movement. The relay is opened in the standby position.
A delay time of 0.5 seconds is set before every door movement.
MOD21
Test of the trap-in protection
The relay generates a test signal upon reaching the CLOSED limit position and awaits actuation of the
STOP circuit as a response to the test signal.
MOD22
Activation of transmission system
radio 1 and radio 4,
test of light grid 1
The relay generates a test signal upon reaching the OPEN limit position and awaits actuation of the
switching strip input as a response to the test signal.
MOD24
Capacitor switching
With every operation command, the relay is closed for approx. 1 second. This relay is used to add an
additional start capacitor required for alternating current applications to ensure safe starting of the motor.
For series STAW with increased switch-on duration.
MOD25
Courtyard light function
With each OPEN command, the relay is closed for 2 minutes and can therefore be used to control a
lighting system.
MOD26
Activation of transmission system
radio 2 and radio 4
Before every DOWN command, the transmission system radio is activated with a pulse. The duration of
activation must be set on the transmission system.
As a result of this activation, travel is delayed by approx. 0.5 seconds.
MOD28
Relay OFF
The relay is switched off as a general rule, the contact is always open.
MOD36
Pneumatic cylinder for locking
the slip door (threshold-free door
system)
With every OPEN command the relay is activated and controls a pneumatic cylinder that mechanically
locks the slip door of the door. The locking position of the cylinder is queried via a limit switch. Only after
this limit switch is released does the door start to move. The relay remains active until the lower end point
is reached again.
MOD37
Testing the stop signal via
transmission system radio 1 and
radio 3
The relay generates a test signal upon reaching the OPEN limit position and awaits an interruption of the
stop circuit as a response to the test signal.
MOD38
Test of light grid 2 (8.2 kΩ),
connection via input 2 (X4 /
11+12)
The relay generates a test signal upon reaching the OPEN limit position and awaits an interruption at
input 2 as a response to the test signal.
MOD 41
Activation transmission system
radio 4 in OPEN direction
The relay generates a test signal upon reaching the CLOSED limit position and awaits an interruption at
input 2 as a response to the test signal.
MOD49
Testing presence and movement
sensors (NC)
The relay generates a test signal each time before closing travel and awaits an interruption of the closing
edge input as a response to the test signal.