Control CS 320 FU / Rev.A 1.01 – 51
11.3
11.3 Explanations of the relay modes:
Explanations of the relay modes:
A.
Traffic light functions
MOD
Description
CLOSED limit
position
OPEN limit posi-
tion
Forewarning
Door movement
MOD1
Red traffic light inside 1
ON / OFF
1
OFF
2
Flashing
Illuminated
MOD2
Red traffic light inside 2
ON / OFF
1
OFF
2
Flashing
Flashing
MOD3
Red traffic light inside 3
ON / OFF
1
OFF
2
Illuminated
Illuminated
MOD18
Red traffic light inside 4
OFF
OFF
Flashing
OFF
MOD23
Green traffic light inside
OFF
Illuminated
2
OFF
OFF
MOD44
Red traffic light
outside
OFF
OFF
OFF
Flashing
3
MOD60
Red traffic light outside 1
ON / OFF
1
OFF
2
Flashing
Illuminated
MOD61
Red traffic light outside 2
ON / OFF
1
OFF
2
Flashing
Flashing
MOD62
Green traffic light
4
OFF
Illuminated
2
OFF
OFF
1
depending on the parameter TL REST
2
With active two-way control: Depending on the UP command inside or outside
3
from intermediate position DOWN to DOWN, also after stop command. Only in CLOSE direction.
B.
Position messages
MOD
Description
Remarks
MOD6
UP limit position
The relay closes the contact when the door is in the OPEN limit position.
MOD7
DOWN limit position
The relay closes the contact when the door is in the CLOSED limit position.
MOD8
Not OPEN limit position
The relay closes the contact when the door is not in the OPEN limit position.
MOD9
Not CLOSED limit position
The relay closes the contact when the door is not in the CLOSED limit position.
MOD10
Intermediate OPEN position (Sect.
OPEN)
The relay closes the contact when the door is in the intermediate OPEN position (Sect. OPEN).
MOD11
Intermediate CLOSED position
(Sect. CLOSED)
The relay closes the contact when the door is in the intermediate CLOSED position (Sect. CLOSED).
MOD12
Intermediate CLOSED position to
CLOSED limit position
The relay closes the contact when the door is in the range between the CLOSED limit position and the
intermediate CLOSED position (Sect. CLOSED).
MOD19
Intermediate OPEN position to
OPEN limit position
The relay closes the contact when the door is in the range between the OPEN limit position and the
intermediate OPEN position (Sect. OPEN).