48 – Control CS 320 FU / Rev.A 1.01
Functional overviews
Function
Description
Adjustment
options
Factory setting
PIN no. 2
Input and selection of a PIN code for programming a service interval.
After inputting the PIN code, the second programming level opens.
Afterwards, a service interval can be entered via the SERVICE parameter. Input level 2
disappears again after the voltage is switched off, or automatically after 10 minutes.
A change to the PIN code can only take place in the second programming level.
0 – 9999
1111
SERVICE
OFF:
Service display not active
Setting a service interval. After the set load cycles are complete, a service message is
issued (LED / LCD). If a relay output is programmed with MOD31, the respective relay
(continuous signal) switches.
Only appears after activation of input level 2 via parameter PIN no. 2.
OFF
0 – 99950
OFF
INVERTER
Activates or deactivates a connected frequency converter. By connecting a frequency
converter to interface X18 the controller becomes an CS 320 FU.
➔
For detailed information refer to the manual for the CS 320 FU.
MOD1:
Operation without frequency converter
MOD2:
Operation with frequency converter
MOD3:
Operation with frequency converter (effective ramp times)
MOD1 – MOD3
MOD1
BRAKE P.OP.*
Initiates the deceleration time SLOW DO. OP. Display in absolute value encoder
increments as a negative value in relation to the upper end switch-off point.
Only applies for OPENING direction of door travel.
-999 – 0
-250
BRAKE P.CL.*
Initiates the deceleration time SLOW DO. CL. Display in absolute value encoder
increments as a positive value in relation to the lower end switch-off point.
Only applies for CLOSING direction of door travel.
0 – 999
250
BRAKE
P.CL.2*
Initiates the delay time DO. MX. Display in absolute value encoder increments as a
positive value in relation to the lower end switch-off point.
If the end positions are changed again (e.g. fine adjustment), the BP2 is deactivated
again (display A) and must be re-programmed.
Only applies for CLOSING direction of door travel.
* Parameters appear only after programming the end positions
0 - UPPER SWITCH
(0 - LOWER SWITCH)
A
SPEED OPEN
Normal speed for OPENING door movement.
MOT.HZ MIN - MAX
50 Hz
SPEED CLOSE
Normal speed for CLOSING door movement.
MOT.HZ MIN - MAX
50 Hz
MX SPEED CL.
Maximum speed for CLOSING door movement (optional).
Parameter appears only after programming BRAKE P. CL.2.
MOT.HZ MIN - MAX
50 Hz
SOFTRUN OP.
Minimum speed for OPENING door movement.
MOT.HZ MIN - 50 Hz
25 Hz
SOFTRUN CL.
Minimum speed for CLOSING door movement.
MOT.HZ MIN - 50 Hz
25 Hz
SPEED UP OP.
Acceleration time between starting command and SPEED OPEN frequency.
Only applies for OPENING direction of door travel.
0.1 – 9.9 s
2.0 s
SPEED UP CL.
Acceleration time between starting command and SPEED CLOSE frequency.
Only applies for CLOSING direction of door travel.
0.1 – 9.9 s
2.0 s
SLOW DO.
OP.
Deceleration time between Brake point OPEN and SOFTRUN OP. frequency
Only applies for OPENING direction of door travel.
0.1 – 9.9 s
2.0 s
SLOW DO.
CL.
Deceleration time between Brake point CLOSE and SOFTRUN CL. frequency
Only applies for CLOSING direction of door travel.
0.1 – 9.9 s
2.0 s