NDX VALVE CONTROLLER
Status
Related events in the event log
Status description
Proposed actions
Default NAMUR
classification
Partial Stroke Test
Running
Partial Stroke test started
Partial Stroke test completed
Partial Stroke test failed
Partial Stroke test cancelled
Device functional test
is running.
Check the test result from DTM/EDD Event
Log.
Function
Check
Calibration Running
Automatic calibration started
Manual calibration started
1point calibration started
Calibration successful
Calibration failed
Calibration failed in tuning
Calibration failed due to
incorrect magnet installation.
Calibration cancelled
Calibration start failed
Device calibration is
running.
Check the result from DTM/EDD Event Log.
Function
Check
Positioner Diagnostics
Status
Related events in the event log
Status description
Proposed actions
Default NAMUR
classification
Total Relay Valve
Travel Limit Exceeded
Total relay valve travel limit
exceeded
Total relay valve travel limit
recovered
Userdefined limit
exceeded.
Review the device performance. If perfor
mance is adequate, increase value of Total
Relay Valve Travel Limit in DTM/EDD Status
Configuration view
Disabled
Total Operation
Time Limit Exceeded
Total operation time limit
exceeded
Total operation time limit
recovered
Userdefined limit
exceeded.
Review the device performance. If perfor
mance is adequate, increase value of Total
Operation Time Limit in DTM/EDD Status
Configuration view.
Maintenance
Required
Supply Pressure
Sensor Failure
Supply Pressure Sensor Failure
Detected
Supply pressure sensor
recovered
Supply pressure mea
surement is faulty.
Control performance
is reduced.
Change the printed circuit board module to
a new one during next maintenance activ
ity. Follow instructions in User Guide.
Failure
Setpoint Sensor
Failure
Setpoint sensor failure
detected
Setpoint sensor recovered
mA measurement
failed.
Change the printed circuit board module to a
new one and calibrate device. Follow instruc
tions in User Guide
Failure
Prestage Shortcircuit
Prestage shortcircuit error
Prestage shortcircuit recovered
Shortcircuit in the
prestage unit. Device
will go to Failsafe
position
Change Prestage unit and calibrate device.
Follow instructions in User Guide
Failure
Position Sensor Failure Position sensor failure
detected
Position sensor recovered
Position measurement
faulty.
Change the printed circuit board module
to a new one and calibrate device. Follow
instructions in User Guide
Failure
Prestage Open circuit
Prestage open circuit error
Prestage open circuit recovered
Prestage wire is cut or
connector is loose.
Change Prestage unit and calibrate device.
Follow instructions in User Guide
Failure
Position Transmitter
Not Connected
Position transmitter
is available. External
supply voltage is not
connected.
Connect external supply voltage or disable
status in DTM/EDD Status Configuration view.
Out of
Specification