Most of the device statuses also create corresponding
events in the event log. These are listed in chapter Para
meterize Online/Status Configuration.
In addition there are a few events which are only logged
in the event history.
•
Power on (External reset)
•
Failsafe activated
•
Device position will go to fail safe position.
Device is not able to follow setpoint.
•
Check additional status for reason for fail safe.
13.5.3.4 Offline Testing
Fig. 67
Test type defines what kind of a test will be executed. Cur
rently there are four options: Multipoint Step Test, Valve
Signature Test, Valve Deadband Test and Partial Stroke Test.
User can use the Template menu to select either default
values or some predefined set of values for the execution
of a test.
Test parameter grid allows entering testspecific parameters
for the selected test. For example for Multipoint Step Test,
user can enter up to 20 test steps by expanding the gird by
clicking the round plus sign at the topright corner of the grid.
Offline test procedure begins by clicking the Next button.
Fig. 68
Fig. 69
When the offline test has been executed, the test success
and possible error messages are shown at the last step of
the process. By clicking Finish button, user is automatically
transferred to the Offline Test Results view, where test results
are automatically uploaded and presented to the user.
13.5.3.5 Offline Test Results
Fig. 70