NDX VALVE CONTROLLER
13.5.2.3 Commissioning
DTM has a guided startup to help you with commissioning
of the device.
Fig. 57
Step 1
. Assembly Parameters
Set assembly parameters and click Next to confirm.
Fig. 58
Step 2.
Click Next to start Calibration.
Fig. 59
Step 3.
Click Finish to complete.
13.5.2.4 Status Configuration
Available statuses can be either disabled or classified to a
certain NAMUR class in Status Configuration view. Status
limits and current value is shown in the same view when
applicable.
Fig. 60
Following table lists all statuses and related events in the
event log that are available from the device. Description,
proposed actions and default NAMUR classification are
also described in the table.
Status configuration view is also available in offline mode.
To send offline parameterization to the device, open the
DTM GUI in online mode and send modifications by clicking
Apply button.