38
NDX VALVE CONTROLLER
Move within
menus &
change values
UP
DOWN
ENTER
BACK
Enter menu &
select / accept
value to change
Cancel actions &
return up one level
Fig. 43
NOTE
Buttons can be used with the cover installed or
removed.
NOTE
In the both ends of the device temperature
range, operation of the LUI might be limited.
12.1
Overview
The NDX Local User Interface (LUI) includes 4 capacitive
touch buttons which can be used with the cover installed
or removed. When power is applied to the NDX, the external
buttons can be used to configure, calibrate, test, and monitor
the status of the device.
The LUI touch buttons area for sensing the touch of the finger
may not be exactly on top of the button symbol but more on
the screen area. This applies to the enclosure type NDX2 with
thick aluminum cover.
Local User Interface (LUI) functions
•
User access control
•
Guidedstartup wizard
•
Calibration: Automatic / Manual / 1point
•
3 point measurement linearization
•
Configuration of the control valve
þ Actuator Type & Valve Type
þ Valve Dead Angle
þ Performance Level
þ Safety Cutoff Range
þ Input Signal Direction
þ Positioner Fail Action
þ Language Selection
•
Monitoring of valve position, target position, input
signal, supply and actuator pressure
•
Local control of the valve
NOTE (NDX1510_)
When installing the cover make sure that the
cover button symbols are at the same position as
the symbols on the LUI module inside the device
NOTE (NDX_511_ and NDX_512_)
When installing the cover check inside to define
it’s correct position. The magnet in the cover
shall be on the wiring terminal side.
NOTE
The LUI touch buttons area for sensing the
touch of the finger may not be exactly on top of
the button symbol but more on the screen area.
This applies to the enclosure types NDX_511_
and NDX_512_ with thick aluminum cover.
12.2
LUI - User access control
User LUI access can be restricted to guarantee safe and
secure process operation. Any user is always able to see all
LUI information without restrictions (read only mode), but
modification of settings or activating any local command
or function can be restricted.
12 LOCAL USER INTERFACE (LUI)