NDX VALVE CONTROLLER
7.1
Installation to Neles Globe
NOTE
The enclosure of NDX meets the IP66 pro
tection class according to EN 60529. Cable
entry needs to be plugged according to IP66
and it is not allowed to mount NDX in a po
sition where the cable entry is pointing up
wards. Based on good mounting practice, the
recommended mounting position is electrical
connections placed downwards. This recom
mendation is shown in our mounting position
coding for control valves.
If these requirements are not fulfilled, and the
cable gland is leaking and the leakage is dam
aging NDX, our warranty is not valid.
MODEL VD25
MODEL VD29
MODEL VD37
MODEL VD48 AND 55
Fig. 13
7.1.1
Installation to Neles Globe (VD29)
1. Mount the magnet holder with magnet to the
actuator coupler, tighten the fixing screw.
Fig. 14
2. Mount the bracket to the actuator, leaving the screws
loose.
Fig. 15
5 mm
6 mm
13 mm or 21/22 mm
Depends on
actuator size
NOTE
Similar mounting steps apply also with other
Neles Globe actuator sizes.
NOTE
The bracket can be rotated 180° or flipped
front/backside. If the bracket is flipped, the
magnet needs to be flipped correspondingly.
If needed, check the magnet installation toler
ances from the picture in section 7.3 “Installa
tion to any linear actuator”
3. Attach the magnet alignment tool to the magnet.
Adjust the position of the bracket so that the
magnet slides smoothly in the magnet alignment
tool groove and tighten the magnet alignment tool
fixing bolts.