NDX VALVE CONTROLLER
5. Adjust the position of the magnet bracket (and the
IEC bracket) so that the magnet slides smoothly in
the magnet alignment tool groove.
6. Tighten the magnet bracket screws.
7. When the magnet moves smoothly in the magnet
alignment tool, that automatically defines the correct
alignment and distance from the device position
sensor. Tighten the IEC bracket to the actuator and
remove the magnet alignment tool.
Fig. 20
8. Mount the device to the IEC bracket by four screws.
Fig. 21
7
LINEAR MOUNTING