PARAMETERS
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 34 of 67
7.3
Hardware configuration parameters
These parameters configure the hardware or provide information about the hardware.
Parameter Description
Default
P.01
Zero Tension Lock
Issuing a Zero Tension Zone 1 or Zone 2 command will
immediately zero the tension value.
The zeroing of tension can be allowed or not when the security
state is locked.
0 = Zeroing tension allowed when security state is locked.
1 = Zeroing tension is not allowed when security state is locked.
0
P.02
Load Cell Excitation Voltage
The load cell excitation voltage can be set to 5V or 7.5V.
0 = 5V (use with non-MAGPOWR load cells with 5V excitation)
1 = 7.5V (always use with MAGPOWR load cells)
1
P.03
Digital Input level Select
Sets the threshold for the digital inputs for either 5 V or 24 V logic.
0 = 5 V logic threshold
1 = 24 V logic threshold
When set for 5 V, the threshold between on and off is 2.5 volts with
20% hysteresis.
When set for 24 V, the threshold between on and off is 12 volts
with 20% hysteresis.
1
P.10
Communications Type
Selects the fieldbus type.
0 = Modbus TCP/IP
1 = Ethernet/IP
2 = PROFINET IO
Power cycle is required for change
to take effect.
0
P.11
IP Address, High Octets
Set the two highest octets
of the IP Address.
Power cycle is required for change
to take effect.
10.0
P.12
IP Address, Low Octets
Set the two lowest octets of the
IP Address.
Power cycle is required for
change to take effect.
0.113
P.13
Subnet Mask, High Octets
Set the two highest octets of the
Subnet Mask.
Power cycle is required for
change to take effect.
255.0
P.14
Subnet Mask, Low Octets
Set the two lowest octets of the
Subnet Mask.
Power cycle is required for
change to take effect.
0.0
P.15
Program Number
The current program number of the software in this product
Set by
factory