COMMUNICATIONS INTERFACE
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 43 of 67
8.5
Alarm
The Alarm cyclic parameter shows the Alarm 1 and Alarm 2 state.
Bit 0 is the status of alarm 1.
Bit 1 is the status of alarm 2.
Bit = 0, Alarm OFF
Bit = 1, Alarm ON
8.6
Command interface
Commands are entered into the
Command Request
register.
Parameters are read or written by a value in the
Command
Request Parameter.
To write a parameter value, the value must be
set in the Command Request Parameter before the Command
Request is entered. See section 8.6.2 for all available commands
and parameters.
After a
Command Request
has been entered the interface will
respond with a reply in the
Command Response.
When reading a
parameter, the
Command Response Parameter
will contain the
value of the parameter. See section 8.6.3 for the command
response messages.
The
Command Response
will show a busy status while executing
commands and once the command processing is complete, the
Command Response
will show either an error message or a
completed message. After the command has returned with either
an error or completed message, a command of 0 must be sent in
the
Command Request
before sending another command.
The commands are used to perform calibrations and zeroing of
tension and also to get and set the value of the parameters in the
DLCA NET-S1.