COMMUNICATIONS INTERFACE
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 50 of 67
8.7.2
Reset non-volatile (NV) memory to defaults
These commands will reset the specified parameters to factory
defaults.
Command
Function
Explanation
0x019
Reset NV Parameters
Only
Reset parameters belonging to
the Parameter class.
0x01A
Reset NV Load Cell
Calibrations Only
Reset parameters belonging to
the Load Cell Calibration class.
0x01B
Reset NV Output
Calibrations Only
Reset parameters belonging to
the Output Calibration class.
0x01C
Reset NV
Communications Only
Reset parameters belonging to
the Communication class.
0x01D
Reset NV All
Reset all the parameters.
8.7.3
Zeroing the tension
The tension can be zeroed by entering the command Zero
Tension Zone 1 (0x01E) or Zero Tension Zone 2 (0x01F).
After zeroing tension zone 2, then tension zone 1 will need to be
zeroed. This is due to the interaction of tension zone 2 on
tension zone 1. Tension zone 1 can be zeroed independent of
tension zone 2.
8.7.4
Calibrate the analog outputs (not normally used)
These parameters set the offset and gain for the analog outputs
to calibrate the outputs to real volts or real current. The
parameters compensate for component tolerances on each DLCA
NET-S1. These parameters are calibrated at the factory and are
not reset during the power-up function 'reset parameters to
default'.
If these need to be changed, connect a voltmeter or current meter
(as appropriate to the output that is being calibrated) and adjust
the value of the parameter until the voltage or current reads the
proper value.
Put the new value of the parameter into the
Command Request
Parameter
before issuing the command.
The output will go into calibration mode only while the command
is active. Once the
Command Request
is returned to 0, the DLCA
NET-S1 will exit from calibration mode.