OPERATION
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 21 of 67
4.1
Zeroing tension display
While displaying tension, press the [
] button for two seconds to
zero the tension in the tension zone being displayed. The outputs
will also be zeroed. After zeroing tension zone 2, then tension zone
1 will need to be zeroed. This is due to the interaction of tension
zone 2 on tension zone 1. Tension zone 1 can be zeroed
independently of tension zone 2.
Connecting the digital input 1 or 2 (zero) to 5V or +24V for
greater than 500 ms will zero the displayed tension and output for
the respective tension zone.
This function will work only when the following conditions are met:
-
When displaying tension and not in the parameter menu
-
When not in calibration mode via either the menu or the
communications
-
If zeroing has not been locked out when a password has locked
the DLCA NET-S1.
4.2
Reset parameters to defaults
Press and hold [+] and [
] while turning power on to the DLCA NET-
S1. The display will show "dEF" for four seconds while all the
parameters are reset to defaults.
This does not reset the analog output calibration parameters in
menus CAL0.1, CAL0.2, or CAL0.4. These parameters are calibrated
at the factory for the component tolerances on each board. The
password and security status is not changed.
4.3
Tension over-range
The tension reading display will flash when the displayed tension
exceeds the maximum tension set in parameter C11.3, or C21.3.
4.4
Password protection
The DLCA NET-S1 allows a password to be set that will prevent
changes to the parameters or performing a calibration. When locked,
all parameters can be viewed. Only zeroing tension is allowed while
the password has locked the DLCA NET-S1, unless zeroing has been
locked out by parameter P.01.