![Manitowoc Marine Q 1000 Service Technician'S Handbook Download Page 96](http://html.mh-extra.com/html/manitowoc/marine-q-1000/marine-q-1000_service-technicians-handbook_701044096.webp)
–86–
DISCHARGE PRESSURE HIGH CHECKLIST
Problem
•
Cause
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
Restricted Condenser Air Flow
•
High inlet air temperature
(110°F/43.3°C max.)
•
Condenser discharge air recirculation
•
Dirty condenser filter
•
Dirty condenser fins
•
Defective fan cycling control
•
Defective fan motor
Restricted Condenser water flow
•
Low water pressure (20 psi min.)
•
High inlet water temperature (9
0°F/32.2°C max.)
•
Dirty condenser
•
Dirty/Defective water regulating valve
•
Water regulating valve out of adjustment
Improper Refrigerant Charge
•
Overcharged
•
Non-condensable in system
•
Wrong type of refrigerant
Other
•
Non-Manitowoc components in system
•
High side refrigerant lines/component restricted
(before mid-condenser)
•
Defective head pressure control valve