–61–
Problem: Water Will Not Run into the Sump Trough
During the Freeze Cycle
Step 1.
Verify water is supplied to the ice machine,
and then start a new Freeze sequence by moving the
ICE/OFF/CLEAN toggle switch to OFF, then back to
ICE.
Step 2.
Wait until the Freeze cycle starts
(approximately 45 seconds – the Freeze cycle starts
when the compressor energizes), and then refer to the
chart.
Important
This restart must be done prior to performing
diagnostic procedures. This assures the ice machine
is not in a Freeze cycle water inlet valve safety shut-
off mode. You must complete the entire diagnostic
procedure within 6 minutes of starting.
Step 2. Checking for Normal Operation
Is Water
Flowing
into the
Water
Trough?
The
Water
Level
Light Is:
The Water
Inlet Valve
Solenoid
Coil Is:
Cause
Yes
Off
Energized
This is
normal
operation.
Do not
change any
parts.
No
On or
Off
Energized
or
De-energized
Proceed to
step 3.
Summary of Contents for Marine Q 1000
Page 1: ... Manitowoc Ice Inc P N 80 1099 9 8 03 ...
Page 2: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 19: ... 9 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ... 10 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ... 24 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 79: ... 69 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 80: ... 70 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 114: ... 104 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 173: ... 163 SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING USING PINCH OFF TOOL ...
Page 177: ......
Page 178: ......