–115–
Fan Cycle Control
(Self-Contained Air-Cooled Models Only)
FUNCTION
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and
opens on a decrease in discharge pressure.
CHECK PROCEDURE
1. Verify fan motor windings are not open or
grounded, and fan spins freely.
2. Connect manifold gauges to ice machine.
3. Hook voltmeter in parallel across the fan cycle
control, leaving wires attached.
4. Refer to chart below.
Specifications
Model
Cut-In (Close)
Cut-Out (Open)
Q200/Q280
Q320/Q370/
Q420/Q450/
Q600
250 psig ±5
(1724 kPa ±35)
200 psig ±5
(1379 kPa ±35)
Q800/Q1000/
Q1300/Q1800
275 psig ±5
(1896 kPa ±35)
225 psig ±5
(1551 kPa ±35)
FCC Setpoint:
Reading
Should Be:
Fan
Should Be:
Above Cut-In
0 Volts
Running
Below Cut-Out
Line Voltage
Off
Summary of Contents for Marine Q 1000
Page 1: ... Manitowoc Ice Inc P N 80 1099 9 8 03 ...
Page 2: ......
Page 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 19: ... 9 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ... 10 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ... 24 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 79: ... 69 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 80: ... 70 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 114: ... 104 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 173: ... 163 SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING USING PINCH OFF TOOL ...
Page 177: ......
Page 178: ......