A1-6
SETTING RANGE
SETTING
FACTORY
USER
PARA.
CONSTANT
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
Frequency Reference 16
0.00
3.11
0: PID control disabled
1: D = Feed Forward
2: D = Feedback
3: Ref PID (D = Feed Forward)
4: Ref PID (D = Feedback)
1
0
PID Control Selection
5: Inverse PID - D = Feed Forward
6: Inverse PID - D = Feedback
7: Inverse PID - Ref PID
(D = Feed Forward)
8: Inverse PID - Ref PID
(D = Feedback)
PID Feedback Gain
0.00 to 10.00
0.01
1.00
PID Proportional Gain
0.00 to 25.00
0.1
1.0
PID Integral Time
0.00 to 360.00
0.1 s
1.0
5.28
PID Derivative Time
0.00 to 2.50
0.01
0.00
PID Offset Adjustment
-100 to 100
1%
0
Integral Value Limit
-100 to 100
1%
100
PID Output Lag Filter Time
0.0 to 10.0
0.1 s
0.0
Feedback Loss
0: Disabled
1: Enabled - Alarm (operation continues)
1
0
Detection Selection
2: Enabled Fault (coast to stop)
Feedback Loss
Detection Level
0 to 100
1%
0
Feedback Loss
Detection Time
0.0 to 25.5
0.1 s
1.0
0: Energy saving disabled
n139
Energy Saving Selection
1: Energy saving enabled
1
0
(V/f control mode)
Note: Energy saving becomes enabled by
V/f control mode
n140
Energy Saving Gain
K2
0.00 to 6550
0.1 or 1
Note 1
n141
Energy Saving Voltage
0 to 120
1%
50
Lower Limit at 60 Hz
n142
Energy Saving Voltage
0 to 25
1%
12
Lower Limit at 6 Hz
n143
Time of Average kW
1 to 200
1
1
(Energy Saving)
(x 24 ms)
(24 ms)
n144
Voltage Limit of Tuning
1 to 100
1%
0%
(Energy Saving)
n145
Step Voltage of Tuning to
100% Output Voltage
0.1 to 10.0
0.1%
0.5%
(Energy Saving)
n146
Step Voltage of Tuning to
5% Output Voltage
0.1 to 10.0
0.1%
0.2%
(Energy Saving)
Pulse Train Input Scaling
100 to 3300
1 (x 10 Hz)
3072
5.11
(30,720 Hz)
0: 1440 Hz / Max. output frequency
1: 1f output
n150
Pulse Monitor Output
6: 6f output
0, 1, 6, 12,
Frequency Selection
12: 12f output
24, 36
0
24: 24f output
36: 36f output
0: Fault - Coast to stop
1: Fault - Ramp to stop (n020)
Modbus Time Out
2: Fault - Ramp to stop (n022)
1
0
5.14
Detection
3: Alarm - operation continues
4: Disabled
Table A1-1. GPD 315 Parameters - Continued