5-31
Continued
E.
n057 :
Multi-function Output 1
Data 6 or 7 : Overtorque
(terminals MA, MB & MC)
Detection
n058 :
Multi-function Output 2
(terminals P1 & PC)
n059 :
Multi-function Output 3
(terminals P2 & PC)
A Form-C contact, or an open collector output, can be programmed to change states during an
overtorque detection condition.
EXAMPLE OF OVERTORQUE DETECTION
n096
setting: 2
— Overtorque enabled, only at set frequency, coast to stop
n057
setting: 6
— Output contact programmed for overtorque detection
n096
setting: 110 % — Level at which overtorque is sensed
n099
setting: 1.0 s
— Time delay before overtorque event occurs
Detection level
(n098 )
Detection
110%
time
OUTPUT
100%
(
n099)
CURRENT/
TORQUE
0
100%
Coast
MOTOR
stop
SPEED
0
RUN
SIGNAL
FAULT
SIGNAL
CONTACT
OUTPUT
(OVERTORQUE
DETECTION)
TERM. M1 & M2)
Overtorque Detection Timing Diagram
5.20 OVERTORQUE DETECTION