![background image](http://html1.mh-extra.com/html/magnetek/gpd-315/gpd-315_technical-manual_3602605036.webp)
4-4
Fault record display
When U-09 is selected, a four-digit box is displayed. The three digits from the right show a fault
description code, and the digit on the left shows the order of fault (from one to four). Number 1
represents the latest fault, and 2,3,4, in ascending order of fault occurrence.
• Example
n
¨¨¨
...... 4-digit numbers
n
: Order of fault (1 to 4)
¨¨¨
: Fault description
“---” is displayed if there is no fault.
(Refer to section 6 for details of fault.)
• Viewing fault record
Press the
¨
or
¨
key to examine the complete fault record.
• Clearing fault record
Set parameter n001 to “6” to clear the fault record. Display returns to “n001” after completion of 6
setting.
Note: Parameter initializing (n001=8,9,10,11) also clears the fault record.
<
>