2-7
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
Table 2-2. V/f Startup Procedure - Continued
Set motor rated current.
(This can be obtained from
the nameplate of the motor.)
Press and hold
until n036 is
displayed on the digital operator.
Then press
.
Use the
&
keys until the
number in the display matches the motor
rated current.
Then press
.
DATA
ENTER
V
V
DATA
ENTER
V
Set the V/f pattern.
Parameters n011 through
n017 set the V/f pattern.
Table 5-4 in section 5.27 lists
recommended V/f patterns.
The numbers in parentheses
shown in the example below
are for a 460V / 60 Hz
variable torque application
(fan or pump).
Set Parameter n011-
Maximum output frequency.
(60.0 Hz)
Press and hold
until n011 is
displayed on the digital operator.
V
PRGM
PRGM
PRGM
PRGM
PRGM
Then press
.
DATA
ENTER
Then press
.
DATA
ENTER
Use the
&
keys until the
desired number is in the display.
V
V
(1)
(1)
(1)