5-13
n032 :
Jog Reference
Factory setting: 6.00 Hz
Range: 0.00 to 400.0 Hz
n050
thru n056 : Multi-function Inputs
Data 10 : Jog Selection
(Term. S1 - S7)
When jog operation is selected (by external Jog and Run signals), the GPD Drive output will ramp
to the output level set by this parameter.
When an external Jog signal is present, it will override the existing operation mode and the GPD
Drive will ramp to the level set by this parameter.
EXAMPLE:
OPERATION BY REMOTE SIGNAL INPUT (RUN & JOG)
Also see descriptions of MULTI-FUNCTION INPUT TERMINALS, paragraph 5.18.
5.12 JOG REFERENCE
FREQ. CMD
n032
JOG
REF.
0
FREQ. CMD
n032
JOG
REF.
0
*
Or FWD
RUN
*
(Term. S1-S7) JOG
RUN
*
(Term. S1-S7) JOG