5-25
Continued
E.
Data 34 : Up/Down Function
Programming data " 34 " for n056 (multi-function input terminal) allows the S6 / S7 inputs to be
used for Up/Down frequency setting.
NOTES:
1. Parameter n055 will not be valid when n056 is set to " 34 ".
2. Jog has priority over Up/Down.
3. Up/Down has priority over Multi-step Frequency inputs.
4. Upper limit speed is set by the formula:
n011
(Fmax) x n033 (Freq. Ref. Upper Limit)
100
5. Lower limit speed is from n034 , Frequency Reference Lower Limit.
6. See section 5.10 for information on the Up/Down hold memory.
EXAMPLE:
n056
Data 34: Up/Down function
GPD DRIVE
S6
UP
S7
DOWN
SC
0V
UP
o o
DOWN
o o
INPUT SIGNAL
Term. S5 Term. S6
FUNCTION
UP
DOWN
Open
Open
HOLD
Closed Open
UP (Frequency command approaches frequency
command upper limit)
Open
Closed
DOWN (Frequency command approaches minimum
output frequency or frequency command lower limit,
whichever is larger)
Closed Closed
HOLD
5.18 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S7)