![background image](http://html1.mh-extra.com/html/magnetek/gpd-315/gpd-315_technical-manual_3602605038.webp)
5-2
A.
n019 :
Accel Time 1
Factory setting (each): 10.0 seconds
n020 :
Decel Time 1
Range (each): 0.00 to 6000.0 seconds
n021 :
Accel Time 2
Factory setting (each): 10.0 seconds
n022 :
Decel Time 2
Range (each): 0.00 to 6000.0 seconds
The GPD Drive incorporates two sets of individually programmable acceleration and deceleration
times.
B.
n050 thru n056 :
Multi-
Data 11 : Accel/Decel Time Selection
function Inputs (Term. S1 thru S7)
By programming data " 11 " into one of the multi-
function parameters (n050 thru n056 ), one of the
multi-function input terminals (S2 thru S7) becomes a
time selection input. When the input terminal (i.e.
external contact) is open, Time 1 (n019 / n020 ) is
selected. When the input terminal is closed, Time 2
(n021 / n022 ) is selected.
C.
n018 :
Accel/Decel Time Setting Unit
Factory setting: 0
Range : 0 = 0.1 seconds
1 = 0.01 seconds
In addition to determining the setting resolution, this parameter controls the range of n019 thru n022 ;
if the resolution is 0.01 sec., the range is 0.00 to 600.00 sec. If the resolution is set to 0.1 sec., the
range is 0.0 to 6000.0 sec.
TIME 1 o
o
o
TIME 2
GPD 315
S5
SC
0V
5.2 ACCEL/DECEL TIME
Summary of Contents for GPD 315