5-28
5.19 MULTI-FUNCTION OUTPUT TERMINALS (Term. MA, MB & MC; M1 & M2)
Table 5-3. Multi-function Output Terminals
Set
Description
Value
Condition
Signal Level
0
Fault
Closed = GPD Drive fault has occurred (except CPF0, CPF1)
1
During operation
Closed = GPD Drive is operating
2
Speed at set frequency
Closed = Frequency Reference = output frequency
See paragraph 5.19A
3
Zero Speed
Closed = GPD Drive is at zero Hz.
4
Frequency detection - low
Closed = Output frequency
≤
n095
.
See paragraph 5.19B
5
Frequency detection - high
Closed = Output frequency
≥
n095
.
See paragraph 5.19C
6
Overtorque detection
Closed = Overtorque detected
(N.O. contact)
See paragraph 5.20
7
Overtorque detection
Open = Overtorque detected
(N.C. contact)
See paragraph 5.20
10
Alarm (minor fault)
Closed = Alarm condition is present
11
During coast to stop
Closed = GPD Drive output base block is active; motor is coasting
12
Local/Remote
Open = Frequency and Run Command by ext. input;
Closed = Frequency and Run Command by Digital Operator
13
Operation ready
Closed = GPD Drive is ready for operation (not faulted)
14
Auto-restart
Closed = During auto-restart operation
15
During Undervoltage
Closed = GPD Drive has an undervoltage fault or warning.
16
During Reverse run
Closed = GPD Drive operation in reverse
17
During Speed Search
Closed = GPD Drive performing a speed search
18
Serial communication
Closed = Command from serial communication
Continued