![background image](http://html1.mh-extra.com/html/magnetek/gpd-315/gpd-315_technical-manual_3602605097.webp)
A2-1
(table continued on next page)
Appendix 2. SPECIFICATIONS
See notes at end of table.
SECTION A. Model No. Related Specifications
230 VAC
Model Number
MVA001
MVA002
MVA003
MVA005
MVA008
MVA011
MVA017
MVA025 MVA033
Max. applicable motor output
1/8 (0.1)
1/4 (0.2)
1/2 (0.4)
1 (0.7)
2 (1.5)
3 (2.2)
5 (3.7)
7.5 (5.5) 10 (7.5)
HP (kW)
(1)
Drive capacity (kVA)
0.3
0.6
1.1
1.9
3.0
4.2
6.7
9.5
13
Rated Output Current (A)
0.8
1.6
3.0
5.0
8.0
11.0
17.5
25
33
Max. Output Voltage (V)
380V to 460V (proportional to input voltage)
Max. Output Frequency (Hz)
400 Hz (programmable)
Rated Input Voltage and
three-phase. 380 to 460 V, 50/60 Hz
Frequency
Allowable voltage fluctuation
-15% to +10%
Allowable frequency fluctuation
±5%
460 VAC
Model Number
- -
- -
MVB001
MVB002 MVB003
MVB005 MVB009 MVB015 MVB018
Max. applicable motor
output HP (kW)
(1)
- -
- -
1/2 (0.2)
3/4 (0.4)
2 (0.7)
3 (1.5)
5 (3.7)
7.5 (5.5) 10 (7.5)
Drive capacity (kVA)
- -
- -
0.9
1.4
2.6
3.7
7
11
14
Rated Output Current (A)
- -
- -
1.2
1.8
3.4
4.8
9.2
14.8
18
Max. Output Voltage (V)
380 to 460V (proportional to input voltage)
Max. Output Frequency (Hz)
400 Hz (programmable)
Rated Input Voltage and
three-phase. 380 to 460 V, 50/60 Hz
Frequency
Allowable voltage fluctuation
-15% to +10%
Allowable frequency fluctuation
±5%
SECTION B. All GPD 315s
Control method
Sine wave PWM (V/f Control or Open Loop Vector)
Frequency control range
0.1 to 400 Hz
Frequency accuracy
Digital command: ±0.01% (14 to 122°F, -10 to +50°C)
(temperature change)
Analog command: ±0.5% (77°F ± 18°F, 25°C ± 10°C)
Digital Operator reference: 0.01 Hz (< 100Hz)
Frequency setting resolution
0.1 Hz (100Hz or more)
Analog reference: 0.06Hz/60Hz (1/1000)
Output frequency resolution
0.01 Hz
Overload capacity
150% of rated output current for 1 minute
0 to 10VDC (20k
Ω
), 4 to 20mA (250
Ω
), 0 to 20mA (250
Ω
) pulse train input,
Frequency Reference Signal
Digital Operator Pot
0.01 to 6000 sec.
Accel/Decel Time
(accel/decel time are independently programmed)
Short-term average deceleration torque (2)
0.2kW: 150%
0.75kW: 100%
Braking Torque
1.5kW: 50%
2.2kW or more: 20%
Continuous regenerative torque: Approx. 20% (150% with
optional braking resistor, braking transistor built-in)
V/f characteristics
Custom V/f pattern
Table A2-1. Standard Specifications
Output
Characteristics
Power
Supply
Output
Characteristics
Control Characteristics
Power
Supply
Summary of Contents for GPD 315
Page 1: ...GPD 315 Technical Manual Magne Tek ...
Page 20: ...1 14 ...
Page 32: ...3 2 ...
Page 76: ...5 40 PID Block Diagram ...
Page 80: ...5 44 ...
Page 96: ...A1 8 ...
Page 100: ...A3 2 ...
Page 102: ...A4 2 ...
Page 110: ...A6 6 ...
Page 114: ......
Page 116: ......