5-15
Continued
n008 : Reference Selection - Digital Operator
Factory setting: 0
Range: 0 or 1
This parameter is only effective when the GPD Drive is in the local mode.
n009 : Frequency Reference Setting
Factory setting: 0
Method From Digital Operator
Range: 0 or 1
This parameter is only effective when the frequency reference is controlled by a digital preset (n024).
SETTING
DESCRIPTION
0
Frequency reference is controlled by the digital operator potentiometer
1
Frequency reference is controlled by a digital preset speed (n024) and is affected by n009.
SETTING
DESCRIPTION
0
key must be pressed in order for the drive to accept the frequency reference.
1
key does not have to be pressed.
The GPD 315 drive responds immediately to the
and
keys.
5.13 LOCAL/REMOTE REFERENCE & SEQUENCE SELECTION