9. Appendix
9-22
8.
Test drive: Start [Cn-00] by pressing [SET] to conduct test drive manually. (JOG
operation speed can be changed in [P3-12].)
* [Up]: Motor forward rotation (CCW)
→
Only operate while you hold down the key.
* [Down]: Reverse motor rotation (CW)
→
Only operate while you hold down the key.
During normal operation, the power input of the servo drive and wiring among
motors are verified as normal.
If the alarm is displayed, it indicates an error in the power circuit, wiring of the
servo motor, or encoder wiring. Turn off power and fix the error using the
information in "[Alarm Codes and Descriptions]."
9.
Operation mode setting: Set
operation mode in [P0-03].
0: Torque control operation
1: Speed control operation
2: Position control
operation
3: Speed/position control
operation
4: Speed/torque control
operation
Speed
operation
setting
Position operation
setting
10.
Perform speed operation with the upper level
controller by adjusting the following parameter
data.
a.
Speed operation setting parameter: [P3-
01]~[P3-20]
b.
Input/output setting parameter: [P2-00]~[P2-22]
c.
Control setting parameter:
[P1-00]~[P1-27]
(Refer to “Appendix 1.”)
11.
Perform position operation with the upper level
controller by adjusting the following parameter
data.
d.
Position operation setting parameter: [P4-
00]~[P4-14]
e.
Input/output parameter setting parameter:
[P2-00]~[P2-22]
f.
Control parameter setting parameter:
[P1-00]~[P1-27]
(Refer to “Appendix 1.”)