Indoor unit
Ceiling Concealed Duct(Low Static)
_
17
Indoor Units
7. External Static Pressure (E.S.P) & Air Flow
(Unit : CMM)
ARNU21GL3G4, ARNU24GL3G4
Setting Value
Static Pressure(mmAq(Pa))
0 (0)
1 (10)
2 (20)
3 (29)
4 (39)
5 (49)
85
10.19
-
-
-
-
-
90
12.18
10.71
11.09
-
-
-
95
13.81
12.34
12.19
-
-
-
100
15.16
13.69
13.38
10.71
-
-
105
16.30
14.83
14.36
11.85
-
-
110
17.31
15.85
15.23
12.86
10.97
-
115
18.27
16.80
16.07
13.82
11.93
-
120
19.26
17.79
16.93
14.80
12.91
10.49
125
20.34
18.87
17.89
15.88
13.99
11.57
130
21.60
20.13
19.01
17.14
15.25
12.83
135
-
21.64
20.36
18.66
16.76
14.35
139
-
-
21.08
19.05
17.34
15.29
Note :
1. The above table shows the correlation between the air rates and E.S.P.
ARNU21GL3G4, ARNU24GL3G4
Fan Performance
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
External Static Pressure(mmAq)
10.0 12.0 14.0 16.0 18.0 20.0 22.0
Air Flow (CMM)
90 SV
100 SV
110 SV
120 SV
130 SV
135 SV