Indoor unit
Ceiling Concealed Duct (High Sensible)
_
29
Indoor Units
10. Installation
• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Air filters
Air intake vents
Air outlet vents
Remote Controller
TEMP
Wired LCD Remote Control
Required Parts
Required Tools
• Connecting cable
• Pipes: Gas side
Liquid side
• Hanging Bolt
(W 3/8 or M10 length 650mm)
• Insulated drain hose
• Additional Drain hose
• Level
• Screw driver
• Electric drill
• Hole core drill
• Flaring Tool set
• Torque Wrenches
• Hexagonal Wrench
• Gas-leak detector
• Thermometer
10.1 Selection of the best location
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension “H” is necessary to get a slope to drain
as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
• The servicing inspection hole in the ceiling should be as
large as the product
• The selection of the servicing hole should be approved by
the customer
[Unit: mm(inch)]
Top view
Front view
[Unit: mm(inch)]
[600(23-5/8) x 600(23-5/8)]
600
(23-5/8)
600
(23-5/8)
1000
(39-3/8)
H = 20(25/32) or more