Units
Model Type Hz Volts Voltage Range
CE
CE
CE
50 220-240
MAX.264
CE
MIN.198
CF
CF
Power Supply
IFM
Input(W)
MCA
MFA
kW
FLA
Cooling Heating
Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where
voltage supplied to unit terminals is not below or above
the listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.
ARNU07GCEA4
ARNU07GCEU4
ARNU09GCEA4
ARNU09GCEU4
ARNU12GCEA4
ARNU12GCEU4
ARNU15GCEA4
ARNU15GCEU4
ARNU18GCFA4
ARNU18GCFU4
ARNU24GCFA4
ARNU24GCFU4
ARNU07GCEA4
ARNU07GCEU4
ARNU09GCEA4
ARNU09GCEU4
ARNU12GCEA4
ARNU12GCEU4
ARNU15GCEA4
ARNU15GCEU4
ARNU18GCFA4
ARNU18GCFU4
ARNU24GCFA4
ARNU24GCFU4
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.00 15 0.024 0.76 85 85
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
1.20 15 0.038 0.97 115 115
CE
CE
CE
60 220
MAX.242
CE
MIN.198
CF
CF
Floor Standing
_
17
8. Electric Characteristics
Indoor unit
Indoor Units