Indoor unit
Ceiling Concealed Duct(Low Static)
_
15
Indoor Units
7. External Static Pressure (E.S.P) & Air Flow
Setting Value
Static Pressure(mmAq(Pa))
0 (0)
1 (10)
2 (20)
3 (29)
4 (39)
5 (49)
60
-
-
-
-
-
-
65
5.03
-
-
-
-
-
70
5.60
4.85
-
-
-
-
75
6.19
5.44
4.57
-
-
-
80
6.79
6.05
5.17
-
-
-
85
7.41
6.67
5.80
4.80
-
-
90
8.05
7.31
6.43
5.44
-
-
95
8.71
7.96
7.09
6.09
4.97
-
100
9.38
8.63
7.76
6.76
5.64
-
105
10.07
9.32
8.45
7.45
6.33
5.08
110
-
10.03
9.16
8.16
7.04
5.79
115
-
-
9.88
8.88
7.76
6.51
120
-
-
-
9.62
8.50
7.25
125
-
-
-
10.38
9.26
8.01
130
-
-
-
-
10.03
8.78
ARNU05GL1G4, ARNU07GL1G4, ARNU09GL1G4
(Unit : CMM)
Note :
1. The above table shows the correlation between the air rates and E.S.P.
ARNU05GL1G4, ARNU07GL1G4, ARNU09GL1G4
Fan Performance
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
External Static Pressure(mmAq)
4.5 5.5 6.5 7.5 8.5 9.5 10.5
Air Flow (CMM)
80 SV
90 SV
120 SV
110 SV
100 SV