8. Electric Characteristics
Indoor unit
26
_
Ceiling Concealed Duct(Middle Static)
Indoor Units
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or
above the listed range limits,
2. Maximum allowable voltage unbalance between phas-
es is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units
Power Supply
IFM
Input(W)
Model
Type
Hz
Volts
Voltage Range
MCA
MFA
kW
FLA
Cooling
Heating
ARNU07GM1A4
M1
50
220-240
Max:264
Min:198
2.00
15
0.136
1.60
190
190
ARNU09GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU12GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU15GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU18GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU24GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU28GM2A4
M2
2.90
15
0.350
2.30
350
350
ARNU36GM2A4
M2
2.90
15
0.350
2.30
350
350
ARNU42GM2A4
M2
2.90
15
0.350
2.30
350
350
ARNU48GM3A4
M3
3.10
15
0.350
2.50
400
400
ARNU54GM3A4
M3
3.10
15
0.350
2.50
400
400
ARNU07GM1A4
M1
60
220
Max:242
Min:198
2.00
15
0.136
1.60
190
190
ARNU09GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU12GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU15GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU18GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU24GM1A4
M1
2.00
15
0.136
1.60
190
190
ARNU28GM2A4
M2
2.90
15
0.35
2.30
350
350
ARNU36GM2A4
M2
2.90
15
0.350
2.30
350
350
ARNU42GM2A4
M2
2.90
15
0.350
2.30
350
350
ARNU48GM3A4
M3
3.10
15
0.350
2.50
400
400
ARNU54GM3A4
M3
3.10
15
0.350
2.50
400
400