Indoor unit
Dip Switch & Group Control Setting
_
1
Dip Switch &
Group Control Setting
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
1.1 Dip Switch Setting
Dip Switch Setting of Indoor unit PCB
For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.
CAUTION
Function
Description
Setting Off
Setting On
Default
SW1
Communication
N/A (Default)
-
-
Off
SW2
Cycle
N/A (Default)
-
-
Off
SW3
Group Control
Selection of Master or
Slave
Master
Slave
Off
SW4
Dry Contact Mode
Selection of Dry Contact
Mode
Wired/Wireless remote
controller
selection of Manual or Auto
operation Mode
Auto
Off
SW5
Installation
Fan continuous operation
Continuous operation Removal
-
Off
SW6
Heater linkage
N/A
-
-
Off
SW7
Ventilator linkage
Selection of Ventilator
linkage
Linkage Removal
Working
Off
Vane selection
(Console)
Selection of up/down
side Vane
Up side + Down side Vane
Up side Vane
Only
Region selection
Selection tropical region
General model
Tropical model
SW8
Etc.
Spare
-
-
Off