Indoor unit
12
_
Fresh Air Intake Unit
Indoor Units
8. Electric Characteristics
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above the listed range
limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units
Power Supply
IFM
Input(W)
Model Type
Hz
volts
Voltage
Range
MCA
MFA
kW
FLA
Cooling Heating
ARNU48GBRZ4
BR
50
220-240
Max: 264
Min: 198
1.5
15
0.20
0.78
169
169
ARNU76GB8Z4
B8
2.7
15
0.38
1.36
230
230
ARNU96GB8Z4
B8
3.7
15
0.38
2.15
360
360
ARNU48GBRZ4
BR
60
220
Max: 242
Min: 198
1.5
15
0.20
0.78
169
169
ARNU76GB8Z4
B8
2.7
15
0.38
1.36
230
230
ARNU96GB8Z4
B8
3.7
15
0.38
2.15
360
360