CE/CF Chassis
Floor Standing
_
9
5. Wiring Diagrams
Indoor unit
Indoor Units
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function
Description
Setting Off
Setting On
Default
SW1
Communication
N/A (Default)
-
-
Off
SW2
Cycle
N/A (Default)
-
-
Off
SW3
Group Control
Selection of Master or Slave
Master
Slave
Off
SW4
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote controller selec-
tion of Manual or Auto operation Mode
Auto
Off
SW5
Installation
Fan continuous operation
Continuous operation Removal
-
Off
SW6
Heater linkage
N/A
-
-
Off
SW7
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal
Working
Off
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side Vane
Up side Vane Only
Region selection
Selection tropical region
General model
Tropical model
SW8
Etc.
Spare
-
-
Off
CONNECTOR NUMBER SPEC. DESCRIPTION
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-COMM
CN-EEV
CN-PIPE_IN
CN-PIPE_OUT
CN-ROOM
CN-REMO
CN-OPTION
CN-ZONE
CN-DISPLAY
CN-CC
CN-EXT
AC power supply
Fan motor output
Fan motor output
Communication
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Option PCB
Zone controller
RF Remote controller
Dry contact
External On/Off
AC Power line input for indoor controller
Motor output of BLDC
Motor output of BLDC
Communication between indoor and outdoor
EEV Control output
Pipe in thermistor
Pipe out thermistor
Room thermistor
Remote control line
Communication between main and option
Zone control line
RF Remote control line
Dry contact line
External On/Off signal input