Indoor unit
18
_
Ceiling Concealed Duct(High Static)
Indoor Units
6. Capacity Tables
Heating capacity
Notes:
TC: Total Capacity(kW)
1. Capacity tables show the representative value of conditions which may occur.
2.
is shown as reference. When selecting the outdoor units, avoid the out-
door air temperature range shown by
.
3. In accordance with operation limits of outdoor unit, applicable range of capac-
ity tables is different.
4. Refer to Capacity Correction Factor in the outdoor unit PDB for the actual per-
formance data of each indoor unit and outdoor unit combination.
Capacity
Index
Outdoor air
temp.
DB(°C) WB(°C)
Indoor air temp. (DB, °C)
16 18 20 21 22 24
TC TC TC TC TC TC
kW kW kW kW kW kW
-24.8 -25.0 18.2 18.2 18.1 18.1 18.1 18.0
-21.8 -22.0 22.0 22.0 21.9 21.9 21.9 21.8
-19.8 -20.0 23.2 23.2 23.0 23.0 23.0 22.9
-18.8 -19.0 23.8 23.6 23.6 23.6 23.5 23.5
-16.7 -17.0 24.8 24.8 24.8 24.7 24.7 24.7
-14.7 -15.0 26.1 26.1 26.0 26.0 26.0 25.8
-12.6 -13.0 27.3 27.1 27.1 27.1 27.0 27.0
-10.5 -11.0 28.5 28.5 28.3 28.3 28.3 27.5
-9.5 -10.0 29.1 29.1 28.9 28.9 28.9 27.5
-8.5 -9.1 29.6 29.6 29.4 29.4 29.4 27.5
-7.0 -7.6 30.5 30.3 30.3 30.2 29.5 27.5
-5.0 -5.6 31.6 31.6 31.5 30.5 29.5 27.5
-3.0 -3.7 33.1 32.3 31.5 30.5 29.5 27.5
0.0 -0.7 33.7 32.6 31.5 30.5 29.5 27.5
3.0 2.2 34.6 33.5 31.5 30.5 29.5 27.5
5.0 4.1 35.2 33.5 31.5 30.5 29.5 27.5
7.0 6.0 35.5 33.5 31.5 30.5 29.5 27.5
9.0 7.9 35.5 33.5 31.5 30.5 29.5 27.5
11.0 9.8 35.5 33.5 31.5 30.5 29.5 27.5
13.0 11.8 35.5 33.5 31.5 30.5 29.5 27.5
15.0 13.7 35.5 33.5 31.5 30.5 29.5 27.5
28.0