7 ADMINISTRATION
56
7.8
Factory Resetting a Site Controller
While unlikely, there may be a time when circumstance leaves a site controller in an
unknown, unreachable, or otherwise unrecoverable state where a factory reset is
necessary. A full factory reset of your NorthStar lighting controller is accomplished
via the Backup/Restore tab within the Config screen, or manually using buttons on
the site controller.
WARNING:
A factory reset will interrupt lighting service and remove all configured
Lights, Sensors, Zones, and Scenes, and return your site controller to its factory
default state. Do not perform a factory reset unless it is your intention to delete all of
this information.
To factory reset a NorthStar site controller using the user interface:
1.
Log in to the site controller you
wishto reset, then click
Config -
Backup/Restore
to open the
Backup/Restore
tab.
2.
Verify you have a current backup of
your system. For more information
on backing up the system, see
Backing up and restoring a system
configuration on page 55.
3.
Click the
Factory Reset
button to
open the factory reset site controller
pop-up window.
4.
Click the
Factory Reset
button to
reset the site controller, or the
Cancel
button to return to the
Backup/
Restore
menu without resetting.
To factory reset a NorthStar site controller using the side buttons:
1. Push and hold button 1 on the side of the NorthStar site controller.
2.
The bottom LED (LED 3) will glow amber for 2 seconds, during which the unit
will return to factory defaults.
3. When the bottom LED turns off, release the button.
SNAP Antenna
Wi-Fi Antenna
Button 1
Button 2
Button 3
Ethernet Port
Input Voltage
micro-B USB Port
Cellular Antenna
(Optional)
USB Standard-A
Receptacle
WEB
VERSION