Electrical connection
Leuze electronic
LES 36
47
TNT
35/7-2
4
V
Cascading output OutCas
In order to operate several Light section sensors cascaded this output must be connected
directly to the trigger input of the following sensor. Detailed information on this topic can
be found in Chapter 4.2.4. The internal equivalent circuit is shown in Figure 6.6.
Output "ready" OutReady
This output indicates operational readiness of the sensor. The state of the output corre-
sponds to the state of the green LED (see "LED status indicators" on page 52).
6.3.2
Connection X2 - Ethernet
Attention!
All cables must be shielded!
The LES makes either the Ethernet interface available as host interface.
Preferably, please use the ready-made cables "KS(S) ET-M12-4A-…", see
Chapter 15.2.3.
Ethernet cable assignment
Figure 6.7:
HOST / BUS IN cable assignments on RJ-45
Notice for connecting the Ethernet interface!
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed.
The Rx+/Rx- and Tx+/Tx- wires must be stranded in pairs.
Use CAT 5 cables for the connection.
X2 (4-pin socket, D-coded)
Pin
Name
Core color
Comment
1
Tx+
ye
Transmit Data +
2
Rx+
wh
Receive Data +
3
Tx-
OR
Transmit Data -
4
Rx-
bu
Receive Data -
Thread
FE
-
Functional earth (housing)
Table 6.4:
Pin assignment X2
Tx+
1
2
3
4
Rx+
Rx-
Tx-
X2
M12 socket
(D-coded)
Tx+
1
2
3
4
Rx+
Rx-
Tx-
X2
RJ 45
Tx+ (1)
Tx- (2)
Rx+ (3)
Rx- (6)
1
8
Twisted pair
Twisted pair