Integrating the LES in the process control (Ethernet)
Leuze electronic
LES 36
107
TNT
35/7-2
4
V
Get Single User parameter
Status of the transmission of X-coordinates in measure mode
When using parameter ID 0x07D4, sensor control command 0x005B can be used to check
whether X-coordinates are output.
When using sensor control command 0x005B with parameter ID 0x07D4, one word of user
data is transmitted to the sensor:
The sensor responds with 0x005C and returns one word of user data.
If
OF=0
then X- and Z-coordinates are transmitted.
If
OF=1
then only Z-coordinates are transmitted (X-coordinates are deactivated).
Querying the transmission pause between the Z- and X-data packets
When using parameter 0x07D8, sensor control command 0x005B can be used to query the
duration of the transmission pause between the Z- and X-data packets.
When using sensor control command 0x005B with parameter ID 0x07D8, one word of user
data is transmitted to the sensor:
The sensor responds with 0x005C and returns one word of user data.
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
0
0
0
0
0
1
1
1
1
1
0
1
0
1
0
0 Parameter ID for Disable x-Output = 0x07D4
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
OF
OF
= Output Flag
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
0
0
0
0
0
1
1
1
1
1
0
1
1
0
0
0 Parameter ID for transmission pause = 0x07D8
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
-
-
-
-
-
-
-
-
-
-
-
-
P4 P3 P2 P1 Duration of the transmission pause between the
Z- and X-data packets in 0.1ms increments
(0 = 0.1ms … 9 = 1.0ms)