Diagnostics and troubleshooting
Leuze electronic
LES 36
127
TNT
35/7-2
4
V
12.3
Error messages in display (starting from firmware V01.40)
Only 1 error can be shown in the display. In the event of an error, the
first line of the display shows an error message and the second line
displays a plain-text message.
Note!
If deviating error messages occur, contact your Leuze distributor or service organization.
Please disconnect the sensor from the supply voltage and eliminate the cause of the error.
If a short-circuit occurs on the output, the following is displayed:
Please eliminate the cause of the error.
Note!
Acknowledging the error with the "Enter" button on the membrane keyboard causes a soft-
ware reset of the sensor. During this time, the sensor is not ready - this can be seen at: X1
pin 4: Out Ready and Ethernet protocol: "Status".
The sensor starts automatically and is then ready again. An Ethernet connection must be
re-established.
Error
Possible error causes
Measures
Error: 001xx, 005xx, 006xx EMC interference
Check wiring, shield sensor.
Error: 00302, 00309,
00402, 00403
Ambient temperature too
high
Select installation space with a lower temperature.
Error: 01000
Supply voltage when
switching on too high
Check supply voltage.
Error: 01001
Supply voltage when
switching on too low
Check supply voltage.
Output Overload
Short-circuit on output,
EMC interference
Check wiring, shield sensor.
Table 12.3:
Error messages in display
Error: 01001
Supply. Volt.
Output Overload
Reset -> Enter